MIL-HDBK-1027/1B
Table 12 (Continued)
19F4 and 19F4A Structures
________________________________________________________________
AGENT USAGE
________________________________________________________________
CLASS
NO. OF
AFFF
WATER
OF
FIRES/
NO. OF
3%
TIME
FIRE
CLASS
HOSES
L/s
min
First Day PM
B
6
2 - 65 mm
16
5
Second Day PM
B
6
2 - 65 mm
16
5
B
3
2 - 65 mm
16
3
________________________________________________________________
Notes: 1. The design water demand should be 8 + 8 + 16 + 16 =
48 L/s for the occasional times when two 64 mm and
two 38.1 mm cooling water hoses are used together.
This is the total demand for the structure. Do not
add in the water for foam.
2. The maximum 3 percent foam solution demand should be
16 + 16 = 32 L/s.
________________________________________________________________
TOTAL UTILITIES
________________________________________________________________
CLASS
WEEKLY
Propane
3 414 593 L
10 243 779 L
Water
136 440 L
409 320 L
AFFF Concentrate (100%)
3923 L
15 160 L
PKP
None
________________________________________________________________
Notes: 1. The water category includes the water portion of the
AFFF (97 percent water, 3 percent AFFF for design)
and the flush deck nozzle water.
2. 46 percent of the water usage for a 2-day class occurs
occurs on the first day of class. However, since the
whole course is taught in one day to the accelerated
students, the design daily water consumption equals
the full class value.
117