MIL-HDBK-1191
APPENDIX A
ARCHITECTURAL AND ENGINEERING DESIGN REQUIREMENT
LEGEND and NOTES
b.
CLG HT.
Maximum ceiling height in millimeters
(4 characters).
2400mm
=
7'- 10.5" corresponds to 8'-0"
2600mm
=
8'- 6.4"
corresponds to 8'-6"
2700mm
=
8'- 10.3" corresponds to 9'-0'
2900mm
=
9'- 6.2"
corresponds to 9'-6"
3000mm
=
9'- 10.1" corresponds to 10'-0"
A
=
If this area is combined with a delivery room,
provide 3000mm (10'-0") ceiling height, minimum.
If not combined, provide 2400mm (8'-0") CLG HT.
B
= 3000mm (10'-0") minimum.
VAR
= Varies (designers choice)
c.
D00R SIZE. First line is minimum door width in millimeters
(4 characters). Second line is door width in feet and inches.
450mm
corresponds to 1'-6"
900mm
corresponds to 3'-0"
1050mm
corresponds to 3'-6"
1200mm
corresponds to 4'-0"
A
=
Pair 750mm (2'-6") doors.
B
=
Pair 900mm doors.
C
=
Pair 1050mm doors.
D
=
Double door, 1200mm and 450mm
E
=
Pair 900mm doors or 1200mm doors as directed by using
service.
F
=
900mm between scrub room and nursery.
1200mm between delivery room and nursery.
G
=
In clinics, provide 1050mm.
In hospitals, provide double door, 1050mm and 450mm.
H
=
2400mm (8'-0"), pair 1200mm doors, by 2600mm(8'6")
breakaway glass doors or double door 1200mm and
450mm
as directed by using service.
I
=
3000mm (10'-0") by 3000mm (10'-0") minimum. Number as
required by dock.
J
=
Main OR door, pair 900mm doors. Staff door from
clean corridor, 1200mm. Door to sub-sterile, 1050mm.
K
=
Main OR door, pair 900mm doors or 1200mm and 450mm or
1050 mm and 450 mm as directed by using service.
Staff door from clean corridor, 1200mm. Door to
sub-
sterile, 1050mm.
L
=
Darkroom door. Provide revolving door or light tight
door, or vestibule entry, as appropriate.
M
=
Open (no door) or 900mm door as directed by using
service.
N
=
Open (no door) or 1200mm door as directed by using
service.
SP
=
Special, designers choice.
VAR
=
Varies, designers choice.
VET
=
Special door in veterinary facility.
See Architectural Note 13.
OPEN =
No door required.
Apdx A-4