MIL-HDBK-1191
APPENDIX A
ARCHITECTURAL AND ENGINEERING DESIGN REQUIREMENT
LEGEND and NOTES
5.
ELECTRICAL. (20 characters).
a.
LIGHT.
LEV
Maximum general lighting level in lux (4 characters).
First line is general lighting level, second
line is task lighting.
LUX
corresponds to Footcandles
100
10
150
15
200
20
300
30
500
50
700
70
1100
100
1600
150
2100
200
N
Lighting Notes (1 character).
Second line is second note.
A.
Provide full-range dimming in room or special task area.
B.
Provide recessed ceiling exam fixture with high color
rendering type (80 minimum CRI) lamps and 1100 lux task
C.
Provide high color rendering index type (80 minimum CRI)
lamps.
D.
Provide O.R. Type Light Fixture or exam Light with dimmer
at task location.
E.
Explosion Proof design typically required.
F.
Provide multi-level switching with conventional on/off
switching. Provide lighting control at individual task
location where practical.
G.
Provide Safelight for film processing as required by
Equipment List.
H.
Provide full-range dimming at task location.
I.
full-range dimming.
Apdx A-7