MIL-HDBK-1191
APPENDIX A
ARCHITECTURAL AND ENGINEERING DESIGN REQUIREMENT
LEGEND and NOTES
8.
The acoustical noise level in the room is the design value for
the NC-Level for the background (ambient) noise level.
9.
The STC specifies the performance of the room enclosure in
isolating against airborne sound. Where no door is specified,
the remainder of wall partition/ceiling system should still be
designed to this value. This design value is generally
considered as a minimum rating.
10. Seamless epoxy coating shall be used on all walls throughout
the veterinary facility. Concrete block substrate shall be
vermin-proof construction with flush joints.
11. Seamless epoxy coating shall be used on ceilings in the
veterinary facility. Gypsum wallboard substrate shall consist
of two layers of fiber reinforced wallboard. Ceiling shall
have coved corners.
12. Provide non-slip finishes in corridors and all areas where
pedestrian traffic is anticipated. Provide smooth finish where
greater degree of cleanability is required (under cage racks
for example).
13. Provide vermin proof hollow metal doors, 48 inch by 96 inch,
with 12 inch by 12 inch red glass vision panel and recessed
hardware. Provide door seals. Do not provide door lock.
4.
STRU FLR LOAD.
Floor Load in kilo-Pascal (4 characters).
kPa
corresponds to pounds/SF (PSF)
3
60
4
80
5
100
6
125
7.5
150
10
200
12
250
13
275
17
350
A
=
Design for actual wheel loads or 7.5 kPa
(150 psf) minimum.
B
=
Design for actual equipment loads or
7.5 kPa (150 psf) minimum.
C
=
Design for actual equipment loads or
5 kPa (100 psf) minimum.
D
=
Design for actual weight of shelves plus
55 kg/filing meter (3.1 lbs/filing in.)
or 7.2 kPa (150 psf) minimum on the floor.
Apdx A-6