Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
connection, complete with 50-mm [2-inch] drain, 20-mm [3/4-inch] hose thread supplies shall be
provided in standard manufactured recessed wall box with single-face plate. Boxes shall be
constructed of plastic or sheet steel. Steel boxes shall have a corrosion-resistant epoxy enamel
finish. Boxes shall be mounted a minimum of 865 mm [2 ft-10 inches] above the finish floor.
Electrical outlets for both washer and dryer shall also be provided.
8-7
PIPE INSULATION. Insulation type shall be
fiberglass, closed cell foam, or
phenolic
foam.
8-7.1
Domestic service hot water piping. Minimum pipe insulation performance shall be in
accordance with the requirements of the latest edition of ASHRAE/IESNA 09.1.
8-7.2
Domestic service cold water piping shall be insulated with a minimum of 13-mm
[-inch] insulation with vapor jacket
8-7.3
Roof drain piping. Provide 25-mm [1-inch] thickness insulation on all horizontal
piping.
SOW-122