UFC 4-730-10
15 June 2006
Design the HVAC system to meet the requirements of the most current edition of the
International Mechanical Code (IMC); UFC 3-410-01FA, Heating, Ventilating, and Air
Conditioning; and UFC 3-410-02A, Heating, Ventilating, and Air Conditioning (HVAC)
Control Systems. Comply with AT requirements in the design of the HVAC system (See
paragraph 3-9).
To ensure durability, consider climate conditions, high humidity, industrial atmosphere,
salt water exposure, or other adverse conditions when selecting exterior HVAC
components.
3-6.3
Fire Protection.
Design fire protection and life safety to comply with UFC 3-600-01, Fire Protection
Engineering for Facilities and the National Fire Protection Association (NFPA)
Standards, latest editions. Fire Stations must be completely protected with automatic
sprinklers.
3-6.4
Electrical.
Provide electric service and distribution equipment, wiring receptacles and grounding,
interior and exterior lighting and control, emergency lighting, telephone, communication
systems, fire alarm, and intrusion systems in accordance with NFPA 70, National
Electric Code; UFC 3-520-01, Interior Electrical Systems; and the latest installation
design requirements. See the latest edition of Electric Current Abroad, U.S.
Department of Commerce, to determine voltages and cycles in overseas locations.
Service grounding system and all wiring methods must meet the current NFPA 70
requirements. All service equipment must be Underwriters Laboratories (UL) listed.
Alternately, published proof from an approved independent testing laboratory may be
provided.
3-6.4.1
Lighting.
Provide lighting and control systems throughout the facility in accordance with UFC 3-
530-01, Lighting Design and Controls. Additional lighting criteria for specific spaces
within a Fire Station are provided in Chapter 4.
3-6.4.2
Emergency Power.
Provide 100% emergency generator back-up power for HQ/Main and Large HQ
stations. For Satellite stations, provide emergency back-up power, at a minimum, for
the following spaces/systems:
Apparatus Bay lighting and doors,
Watch Desk/Dispatch and all associated equipment,
IT Room systems related to the Dispatch and communication functions,
and
3-4