UFC 4-730-10
15 June 2006
TABLE 4-29.0. VENDING
The vending area accommodates two or more vending machines for snacks and drinks. The
Description/
vending area should be conveniently located for the use of firefighters and fire station staff.
Usage
Do not place vending machines in the Day Room or Lobby. Recommended locations include
the Recreation Room (if provided) or an alcove off of a main hallway.
2.4 m (8 ft.) minimum.
Min. Ceiling Ht.
Walls. Provide a low-maintenance, durable finish such as egg-shell latex paint.
Floor. Provide low-maintenance sheet or tile vinyl flooring material with rubber base.
Ceiling. Provide ACP or painted gypsum ceiling.
None required.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum.
HVAC
Provide Fire Protection System per Paragraph 3-6.3.
Fire Protection
Provide outlets per code. Provide outlets and power required by vending machines.
Power
215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
None required.
Casework
Furnishings
Fixtures &
Equipment
(FF&E)
Special
Requirements
4-34