UFC 4-730-10
15 June 2006
TABLE 4-31.0. EOC SITUATION ROOM
This Emergency Operations Center Situation Room is a specialized conference room used in
Description/
cases of major operations to manage and coordinate rescue and emergency service efforts, if
Usage
required by the Installation mission. It should be set-up to handle planned and ad-hoc meetings
2.4 m (8 ft.) minimum.
Min. Ceiling Ht.
Walls. Provide a low-maintenance, durable finish such as egg-shell latex paint.
Floor. Provide low-maintenance sheet or tile vinyl flooring material with rubber base.
Consider providing durable commercial carpeting.
Ceiling. Provide ACP ceiling.
None required.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum.
HVAC
Provide Fire Protection System per Paragraph 3-6.3.
Fire Protection
Provide outlets per code and as needed to support all equipment.
Power
Provide Lighting System per Paragraph 3-6.4.1.
Lighting
CCTV. Provide outlets required to support equipment.
Communication
CATV/Internal Video. Provide outlets required to support equipment.
PA/Audio. Provide a speaker and a microphone.
Telephone. Provide regular and secure multi-telephone line required to support telephone and
fax.
Data. Provide regular and secure data outlets to support required equipment.
Security. None required.
Consider providing built-in case work such as a counter and base cabinets.
Casework
Provide conference table, conference room chairs, side tables, retractable projector screen, and
Furnishings
overhead projector, other audio/visual equipment, televisions (consider flat screen for wide
Fixtures &
angle viewing), wall-mounted grid map and map racks, and tack and dry-erase boards.
Equipment
(FF&E)
Locate EOC Situation Room in an interior area of the building, adjacent to the Dispatch.
Special
Classified information may be accessed in this room. If so, address security, visibility, and data
Requirements
handling issues.
Provide an STC rating of 50 or better.
4-36