UFC 4-740-02
26 September 2006
TABLE 4-27. PHYSICAL THERAPY/REHAB TRAINING
This optional office provides a space for staff to meet with customers and rehabilitate
Description/
injuries. A private office is preferred, but a workstation may be acceptable if it is large
Usage
enough to accommodate the equipment and private consultation with the customer.
Service Exception: The Navy does not support this space. In Air Force facilities, this
space should be located in the Health and Wellness Center. In Marine Corps facilities,
this space could be adjacent to or combined with the fitness assessment room (see
Table 4-26).
2.74 m (9 ft.) minimum.
Min. Ceiling Ht.
Walls. Painted gypsum wall board or vinyl wall covering.
Floor. Carpet with vinyl or rubber base.
Ceiling. ACP.
None required.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum. Provide dedicated controls.
HVAC
Provide system per Section 3-5.3.
Fire Protection
Power
Provide a minimum of one quad outlet in closed offices on at least three walls. Gang
outlets with data and telephone. Workstations should provide at least one quad outlet
per staff. Provide additional dedicated outlet to accommodate the fitness equipment.
540 Lux (50 ft. candles). General ambient fixtures.
Lighting
CCTV. None required.
Communication
CATV/Internal Video: None required.
PA/Audio: Provide a speaker.
Telephone. Provide one line.
Data. Provide one outlet at desk and one outlet at the fitness equipment.
Security. None required.
None required.
Casework/
Built-in
Equipment
Office furniture: desk, credenza, filing cabinet, desk chair, and two side chairs.
Furnishings
Fixtures &
Cardiovascular fitness equipment.
Equip. (FF&E)
Provide a height-adjustable physical therapy table for examinations and manipulation.
Special Req.
Locate offices on exterior wall and provide windows for natural light admission.
Provide side lights next to the office doors for supervision and security.
May provide a separate but adjacent space to contain a stainless steel, therapeutic
spa tub for additional rehabilitation functions. Criteria for the spa tub area, particularly
flooring, are similar to those for the optional hot tub (see Table 4-18), and that criteria
should be used for a spa tub area.
For use during project execution by the appropriate Service agency
Staff.
Occupancy
Customers.
Min. net m2 (ft2)
4-35