UFC 4-740-06
12 January 2006
3-5.3.11.4 Provide audio and visual notification devices/strobes in accordance with
NFPA 72 and UFC 4-021-01.
Note: Army and Navy require the following additional criteria: Provide a voice
evacuation system that is capable of accepting input from a remote location. This
system must be UL listed for fire alarm use. The voice evacuation system will satisfy
the requirements of the Mass Notification System. Provide a single type of visual
notification device that will serve as the fire alarm visual alarm notification and as the
Mass Notification System visual alarm notification that complies with NFPA 72 and is
labeled "Alert." The spacing and location of the visual notification devices must meet
the requirements of NFPA 72.
3-5.3.11.5 The signal type/tone will be the same throughout the building, and will be
heard on the playgrounds. Sufficient alarm notification devices will be provided so that
the signal is not excessively loud in any location (15 dB above ambient is the target
level).
3-5.3.11.6
Provide manual pull stations inside the facility at each exterior exit door.
3-5.3.11.7 Building smoke detection is not required and should not be provided
except for the one smoke detector that is required by NFPA 72 to be located over the
fire alarm control panel. Heat detectors are not required in any area because the facility
is fully sprinkled. Smoke detectors must be installed in HVAC ducts as required by
NFPA 90A.
3-5.3.11.8
Provide either a graphic or alphanumeric annunciator at the front desk or
vestibule.
3-5.3.11.9 Provide and install a fire alarm transmitter compatible with the installation
fire alarm receiving equipment to transmit fire alarm and system supervisory signals to
the installation fire alarm reporting center. Consult with the Installation Fire Chief or fire
system maintenance activity. This may be a sole source item.
3-5.4
Electrical.
Provide electric service and distribution equipment, wiring receptacles and grounding,
interior and exterior lighting and control, emergency lighting, telephone, communication
systems, fire alarm, and intrusion systems in accordance with NFPA 70; UFC 3-520-01;
and the latest installation design requirements. See the latest edition of Electric Current
Abroad to determine voltages and cycles in overseas locations. Service grounding
system and all wiring methods must meet the current NFPA 70 requirements. All
service equipment must be Underwriters Laboratories (UL) listed. Alternately, published
proof from an approved independent testing laboratory may be provided.
3-5.4.1
Lighting.
Vary lighting levels and types throughout the Youth Center. Provide a combination of
task and ambient light to create interest. Consider that most public spaces in the Youth
26