JOINT CLUB
7-2.13 STEP M - UTILITY & THERMAL LOADS
7-2.13.1
Building
data
A.
Gross
floor
area
15,649
s.f.
B.
Max. population at one time
550
C.
Max. meals served/day
800
7-2.13.2
Utility
loads
Light and power
Electrical:
A.
465 kva
B.
Water:
Max.
flow
rate,
cold
water
96 gpm
Max.
flow
rate,
hot
water
96 gpm
8,000
gal.
T o t a l flow per day
8,000
gal.
Total
gallons
per
day
C.
Sewage:
7 - 2 . 1 3 . 3 Heating and cooling loads
463 MBTU/hr.
A.
Load
5 9 tons
B.
Air
conditioning:
Tons
of
refrigeration
7-2.13.4
D e s i g n assumptions
All
poli cy and design criteria per DOD 4270.1-M.
A.
Esti m a t e s are for plans shown.
B.
40 N o r t h
heat g a i n
calculations.
C.
Heat
load
in
kitchen
not
included
in
D.
Mechanical
room
ventilated
only.
E.
Single glazing, standard glass.
F.
20% outside air assumed f o r
ventilation
G.
Assumed
perimeter
heat
loss :
40 BTU/hr./ft.
H.
Sewage demand based on
10 gpd per person, max. occupancy.
Lighting
load
assumed
2.5
watts/s.f.
I.
7-12