MEDIUM OFFICERS CLUB
7-4.13 STEP M - UTILITY & THERMAL LOADS
7-4.13.1
Building
data
A.
Gross
floor
area
7,806 s.f.
B.
Max. population at one time
275
C.
Max. meals served/day
400
7-4.13.2
Utility
loads
A.
Electrical :
Light and power
205 kva
B.
Water:
Max.
flow
rate,
cold
water
60 gpm
Max.
flow
rate,
hot
water
60 gpm
T o t a l flow per day
4,000
gal.
C.
Sewage:
Total
gallons
per
day
4,000
gal.
7 - 4 . 1 3 . 3 Heating and cooling loads
A.
Load
290 MBTU/hr.
B.
Air
conditioning:
Tons
of
refrigeration
3 5 tons
7 - 4 . 1 3 . 4 Design assumptions.
A l l policy and design criteria per DOD 4270.1-M.
A.
Estimates are for plans shown
B.
C.
Heat
load
in
kitchen
not
included
in
heat
gain
calculations.
D.
Mechanical
room
ventilated
only.
E.
Single glazing, standard glass.
F.
20%
outside
air
assumed
for
ventilation.
G.
Assumed perimeter heat loss:
40
BTU/hr./ft.
H.
Sewage demand based on 10 gpd per person, max. occupancy.
I.
Lighting
load
assumed
2.5
watts/s.f.
7-32