MIL-HDBK-1005/9A
Table 11 (Continued)
Ship Bilge Pump Data
Ship
Number of
Capacity
Rated Pump
Design
Deck Riser
Class1
Oily Waste
of Each
Discharge
Deck Riser
Height
Pressure2
Pressure3
Transfer
Pump
above
Pumps
gpm(L/s)
psig(kPa)
psig(kPa)
Waterline
(OWTPs)
ft(m)
T-AKR 300
2
50(3.2)
55(16.8)
T-AKR 310
2
50(3.2)
60(413.7)
55(16.8)
T-AO 187
1
100(6.3)
60(413.7)
30(206.8)
22(6.7)
T-ATF 166
1
15(0.9)
60(413.7)
44(303.4)
9(2.7)
T-ARC
2
420(26.5)
25(172.4)
AVB
1
30(1.9)
60(413.7)
30(9.1)
1
Major Surface Ship Classes which will be generating oily waste to be
processed ashore. Refer to SECNAVINST 5030.1, Classification of Naval
Ships and Craft, for description of other classes.
2
Rated discharge pressure at the flow capacity listed. Pump recirculating
relief valve limits discharge pressure at zero flow to 125 percent of
rated discharge pressure listed.
3
Estimate of ship deck riser pressure for shoreside design.
4
(C) indicates that information is classified. Use 3-inch piping for
laterals.
97