MIL-HDBK-1005/9A
a) Small Facilities. Defined as pier facilities with
fewer than 15 homeported vessels. Qdaily is determined by
Equation 3:
EQUATION:
(3)
N
∑ Q peak
Q
Q
=
+
daily
comp
n =1
where
Qdaily
= design daily flow for facility,
gpd(L/day)
Qcomp
= maximum fueling flow per day from shore to
ships, gpd(L/day)
N
= number of ships at piers during maximum
holiday berthing or special peacetime
exercise
Qpeak
= peak daily flow from each ship,
gpd(L/day)(see Table 12)
b) Large Facilities. Defined as pier facilities
where more than 15 ships are homeported. Qdaily is determined by
Equation 4.
EQUATION:
(4)
M
∑
Q daily = Q comp + (1.33
Q average )
n =1
where
Qdaily
=
design daily flow for facility, gpd(L/day)
Qcomp
=
maximum fueling flow per day from shore to
ships, gpd(L/day)
M
=
number of ships at piers during average
daily berthing condition.
Qave
=
average daily flow from each ship,
gpd(L/day) (see Table 12)