MIL-HDBK-1027/1B
Table 7 (Continued)
19F3 and 19F3B Structures
________________________________________________________________
PROPANE USAGE (Continued)
________________________________________________________________
CLASS NO. OF
PROPANE PROPANE TOTAL
OF
FIRES/
DEMAND
USE PER PROPANE/
L/s/min FIRE/L3 CLASS L3
BLDG
FIRES CLASS FIRE TYPE
________________________________________________________________
Second Day (Continued)
B3 or B4
D
12
Pit/Weapon
186
16 725
200 704
Alternate
9
A, B, or C
89
10 584
95 258
144 fires/class
715 000
Class for
2 Days
43 639
Class for
2 Days
________________________________________________________________
Notes:
1.
Propane demand is based on a gas pressure at the
burner of 6.89 kPa except for the bilge and pit
fires which are based on 13.78 kPa.
2. The design propane demand for each building is:
B1 79 + 88 or 167 L/s
B2 9 + 9 or 18 L/s
B3 186 L/s
B4 186 L/s
3. The design propane demand for the four buildings
together is: 168 + 19 + 186 + 186 = 559 L/s
________________________________________________________________
97