TABLE 10-2 INTERNAL LOADS
Space
People
Equipment
Administration & Shop Control
1 / 12 sm
1 PC/ person
Customer Waiting
1 / 3 sm
1 Coffee Pot
Break/Training/Conference
1 / 1.5 sm
2 PC's
Special Environment Repair
1 / 14 sm
21.5 watt / sm
Compact Item Repair
1 / 9 sm
21.5 watt / sm
General Repair
1 / 15 sm
21.5 watt / sm
Tool Room
1 / 12 sm
1 PC/28 sm
PLL & RX/TS
1 / 12 sm
1 PC/28 sm
Weapons Vault
0
None
Comsec Vault
0
None
Corridors
1 / 28 sm
None
Toilet, Shower & Lockers
0
None
10-2.2
Ventilation air calculations. Calculations determining minimum outside ventilation air
shall be provided for each building space. Ventilation rates shall be in accordance with the
current edition of the International Mechanical Code. Outside air quantities will be sufficient to
meet ventilation requirements and, for office type areas, maintain a positive pressure relative to
the outdoors unless noted otherwise.
10-2.3
Exhaust air calculations. Calculations determining minimum exhaust shall be
provided for each exhaust system. Exhaust rates shall be in accordance with the current edition
of the International Mechanical Code.
10-2.4
Piping calculations. Calculations shall be provided for pressure drop calculations for
all piping systems, including head loss calculations for all pumps.
10-2.5
Duct calculations. Calculations shall be provided for sizing all duct systems, including
static pressure drop calculations for all fans. Ductwork layout drawings shall also be provided to
indicate all fittings and devices to substantiate calculations.
10-3
HUMID AREA DESIGN. [Climates which have 3000 hours or more of 19.4 degrees
C or higher wet bulb temperature in combination with an outside design condition of 50 percent
or higher relative humidity, or climates which have 1500 hours or more of 22.8 degrees C or
higher wet bulb temperature in combination with an outside design condition of 50 percent or
higher relative humidity shall be considered humid areas. In other areas that do not meet the
strict definitions of a humid area but experience humid conditions on numerous occasions,
these same criteria shall be used by the designer as appropriate for the facility and the climate.]
In humid areas, all air heating and cooling systems shall be provided, and economizer cycles
will not be allowed. Closet and storage spaces shall have louvered doors, and building return
air shall be drawn through these spaces to a ducted return air system. Cooling coils shall have
a maximum of 315 fins/m to allow for easy cleaning, and shall be sized for a maximum face
SOW-85