Project Name
Project Number
TEMF
Statement of Work
UFC 4-214-02, 24 Jul 03
9-3.3.1
Motor Efficiencies. Minimum motor efficiencies shall be either Energy Star or in
accordance with DOE Buying Energy Efficient Products Recommendations ( refer to
definite purpose, special purpose, special frame, or special mounted polyphase induction
motors are excluded from these efficiency requirements. Motors provided as an integral part of
motor driven equipment are excluded from this requirement if a minimum seasonal or overall
efficiency requirement is indicated for that equipment by the provisions of another section.
9-3.4
Switchboard/panelboard. Dead-front construction, NEMA PB1 and UL 67.
9-4
LIGHTING.
9-4.1
Lighting. Lighting designs will incorporate the necessary hazardous area
requirements of the latest edition of NFPA 70, National Electrical Code. Illumination of the
service bays should consider super T8 fluorescent lighting or High Intensity Discharge (HID)
color corrected metal halide fixtures. The fixture layout must be coordinated with the traveling
bridge crane requirements. Fluorescent fixtures will be used in other areas. Illumination levels
will be in accordance with the IESNA Lighting Handbook. Maintained illumination levels will be
in accordance with the following table:
Table 9.1 - Lighting Levels
FUNCTIONAL AREA
LEVEL IN LUX
Administration and Shop Control
540
Warehouse and Storage
160
Latrines, Showers, and Lockers
160
Break, Training, and Conference
325
Repair and Scheduled Maintenance
325
Bays
Weapons Storage and COMSEC
160
Vaults
325
Repair Shops (General Item, Compact
Item, Special Environment, Battery,
etc.)
Fluorescent lights shall be energy efficient fluorescent with electronic ballast. Lighting in
occupied areas shall be color corrected with a Color Rendering Index (CRI) of 85 or better. For
energy conservation dual switching, occupancy sensors and automatic dimming shall be
considered. [ Design District may review http://www.energystar.gov/products/ for additional
information.]
9-4.2
Exterior. Site and area lighting shall be high intensity discharge (HID).
9-5
POWER AND GROUNDING. Power service to the buildings will be fed underground
from the base electrical distribution system to a pad-mounted transformer located near the
SOW-81