UFC 4-214-02, 24 Jul 03
spaces to be sprinkled] shall be protected by a wet pipe sprinkler system except that sprinklers
may be omitted from small detached buildings of less than 465 square meters which are
separated by more than 15 240 mm in distance from any other buildings. Sprinkler system shall
be designed and installed in accordance with the provisions of NFPA 13, Standard for the
Installation of Sprinkler Systems. Provide hydraulic calculations to support design of the system.
Sprinkler systems shall be hydraulically designed to discharge the following minimum density
over the hydraulically most demanding 278.7 square meter of floor area in the following
locations:
L/min/m2
a. Maintenance Bays including Paint Bays:
10.18
L/min/m2
b. POL Storage Areas:
16.29
L/min/m2
c. Office and Admin Areas:
4.07
L/min/m2
d. All other areas:
8.15
12-3.2
Dry pipe sprinkler system. Provide dry pipe sprinkler system for [describe spaces to
be sprinkled]. Sprinkler system shall be designed and installed in accordance with the
provisions of NFPA 13, Standard for the Installation of Sprinkler Systems. Provide hydraulic
calculations to support design of the system. Dry pipe systems shall be hydraulically designed
to discharge the following minimum density over the hydraulically most demanding 362 square
meter of floor area in the following locations:
10.18 L/min/m2
a. Maintenance Bays including Paint Bays:
16.29 L/min/m2
b. POL Storage Areas:
4.07 L/min/m2
c. Office and Admin Areas:
8.15 L/min/m2
d. All other areas:
12-3.3
POL storage facilities if larger than 465 square meter in area or located within 15 240
mm distance of the structure, require sprinkler protection.
12-3.4
Sprinkler Heads. All sprinkler heads located in finished areas shall be recessed
pendent type.
12-3.5
Covered loading docks shall be fully sprinkled by a suitable sprinkler system.
12-4.1
FIRE PUMP. [Delete requirement for fire pump if adequate water pressure is
available to support the fire protection system provided.] Type of pump shall be in accordance
with Mil Handbook 1008C. ]
12-4.1.1 Electric fire pump. Provide electric driven fire pump and controllers in accordance
with NFPA 20.
12-4.1.2 Diesel fire pump. Provide electric driven fire pump and controllers in accordance
with NFPA 20. Provide a diesel fuel tank in accordance with NFPA criteria.
12-5
BUILDING CONSTRUCTION. Comply with requirements of International Building
Code and NFPA 101Life Safety Code.
12-5.1
Fire Extinguishers and Cabinets. Provide portable fire extinguishers in
accordance with NFPA 10. Provide bracket mounted extinguishers in non-core areas. Provide
semi-recessed aluminum fire extinguisher cabinets with clear view panel in core areas. Provide
fire-rated cabinets in fire-rated wall assemblies.