Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
system types and fuel options to be used. Select a system type below or provide a description
of other acceptable systems as an additional subparagraph. UEPH buildings shall be limited to
individual heat pumps, fan coils, or similar units with individual adjustable thermostat and fan
switch in each space (sleeping room, not module). Coordinate unit locations with installation
facilities engineering personnel (DPW). Most installations prefer that fan coils and similar units
for UEPH modules not be ceiling mounted if located in the living/sleeping room or the service
area; floor mounted units or vertical units are often preferred for ease of maintenance and
minimization of water damage if condensate drains get plugged. A central preconditioned
outside air system, supplying neutral air (at or near room temperature) to each occupied space,
shall also be provided for UEPH buildings. All reasonably equivalent fuel options within a range
of 10 percent based on life cycle cost analysis shall be allowed. The Design District may assist
the Installation in preparation of the fuel life cycle cost comparison.] Additional consideration in
the technical evaluation will be given to systems utilizing energy efficient equipment, additional
space in the mechanical room, and other features which contribute to ease of system operation
and maintenance. Additional consideration will also be given to designs which provide
measures to increase energy conservation or occupant comfort such as division of each unit
into more than one conditioning zone for increased control.
[Edit the following list as applicable for the particular project. If not acceptable, insert "...
(Deleted)" following subparagraph letter and delete remainder of text. If a system type is
acceptable for one facility but not for the others, note what exceptions are not allowed after the
subparagraph title. If the desired system type is different than what is described, modify the
description as required for the particular system desired or provide additional paragraphs as
necessary. Preparer of RFP shall get approval from installation for each system used.]
10-4.1
Incremental equipment. [Provide individual thru-wall self-contained air-to air heat
pumps for each sleeping room and individual space that is to be conditioned.] [Provide
individual thru-wall packaged terminal air conditioning units for each sleeping room and
individual space that is to be conditioned.] [Fan coil units with hydronic heating [and cooling]
shall be provided for each sleeping room and individual space that is to be conditioned.]
10-4.2
Air distribution systems. Heating [and cooling] will be provided from [rooftop air
handling units] [central air handling units] [warm air furnaces] [fan coil units]. [Air handling units
shall deliver air to [variable air volume boxes in] [dual duct boxes in] [induction units in] each
space.] ]. [Air handling units shall deliver preconditioned ventilation air to [fan coil units] [heat
pumps] in each space.] [Designate a maximum area served per individual unit or a maximum
unit size.]
10-4.3
Hydronic distribution systems. Provide pumped [condenser water] [hot water] [and]
[chilled water] piping system[s] with a standby pump provided for each system pump provided.
Chilled water will be provided from [central system] [central equipment indicated]. Hot water will
be provided from [central hot water system] [central steam system and convertor] [ central
equipment indicated]. Condenser water will be from [ground source heat pump system] [central
equipment indicated]
10-4.4
Ground source heat pump systems. Provide a ground source heat pump system with
water source heat pumps. System design shall be in accordance with IGSHPA standards.
Supplemental heating and cooling source shall be as indicated. [Designate a maximum area
served per individual unit or maximum unit size.]
10-4.5
Heating only systems. For spaces where heating only is required, provide [unit
heaters], [fin tube radiation], [cabinet heaters] or [convectors]. Units shall be [hydronic] [electric]
SOW-130