10-13.2.1 Cold aboveground piping. Insulation for minus 34.5 degrees to plus 15.6 degrees C
[minus 30 degrees to plus 60 degrees F] for outdoor, indoor, exposed or concealed
applications, shall be as follows:
10-13.2.1.1 Cellular Glass: ASTM C 552, Type II, and Type III.
10-13.2.1.2 Flexible Cellular Insulation: ASTM C 534, Type I or II with vapor retarder skin on
both sides.
10-13.2.1.3 Phenolic Insulation: ASTM C 1126, Type III.
10-13.2.1.4 Polyisocyanurate Insulation: ASTM C 591, Type I.
10-13.2.1.5 Hot aboveground piping. Insulation for above 15.6 degrees C [60 degrees F] for
outdoor, indoor, exposed or concealed applications, shall be as follows:
10-13.2.2.1 Mineral Fiber: ASTM C 547, Types I, II or III.
10-13.2.2.2 Calcium Silicate: ASTM C 533, Type I indoor only, or outdoors above 121 degrees
C [250 degrees F] pipe temperature.
10-13.2.2.3 Cellular Glass: ASTM C 552, Type II and Type III.
10-13.2.2.4 Flexible Cellular Insulation: ASTM C 534, Type I or II to 93 degrees C [200
degrees F] service.
10-13.2.2.5 Phenolic Insulation: ASTM C 1126 Type III to 121 degrees C [250 degrees F]
service shall comply with ASTM C 795.
10-13.2.2.6 Polyisocyanurate Insulation: ASTM C 591, Type 1, to 149 degrees C [300
degrees F] service.
10-13.3
Equipment. Provide on all equipment when temperatures are below 16 degrees C
[60 degrees F], above 40 degrees C [104 degrees F] or where condensation can occur.
Insulation shall be suitable for the temperature encountered. Insulation shall be formed or
fabricated to fit the equipment. Removable insulation sections shall be provided to cover parts
of equipment which must be opened periodically for maintenance including vessel covers,
fasteners, flanges and accessories. Supply the insulation with manufacturer's recommended
factory applied jacket.