Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
12-6.2.3
Cellular plastics shall not be used as interior wall and ceiling materials.
12-6.2.4 Carpeting and other textile wall coverings shall only be applied as an interior finish if
the material passes the acceptance criteria of the Uniform Building Code (UBC) Standard 8-2,
Test Method for Textile Wall Coverings, conducted by a nationally recognized testing laboratory.
12-7
FIRE ALARM. Provide fire alarm and detection system conforming to requirements
of NFPA 72 and NFPA 101. Fire alarm system shall be addressable (intelligent) and consist of
smoke and/or heat detectors, pull stations, audiovisual devices, control/annunciation panel and
tamper and/or flow connection/supervision to the sprinkler system. Heat detectors are not
required in UEPH buildings. Provide supervision of fire pump where fire pump is provided. [Fire
alarm system shall tie into the base-wide system.]
12-7.1
[ Design Activity shall provide detailed information on the existing base-wide fire
alarm system if one exists. ]
SOW-152