UFC 4-730-10
15 June 2006
TABLE 4-13.0. VEHICLE MAINTENANCE EQUIPMENT STORAGE
Vehicle Maintenance Equipment Storage is tied to the Vehicle Maintenance Bay and is used to
Description/
store spare parts and tools required for vehicle maintenance and service. It is only provided if
Usage
required by Installation mission requirements. It should accommodate shelving storage and
adequate floor area for storage of large items such as tires and wheels.
4.26 m (14 ft.) minimum.
Min. Ceiling Ht.
Walls. CMU. Provide epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may
also be acceptable.
Ceiling. Ceiling not required; however, consider finishing exposed structure. Consider
coordinating mechanical, electrical, and plumbing components. Note that none of the ceiling
components can be located below minimum ceiling height.
None required.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum.
HVAC
Provide Fire Protection System per Paragraph 3-6.3.
Fire Protection
Provide outlets per code.
Power
215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. Provide one line with internal two-way communication.
Data. None required.
Security. None required.
None required.
Casework
Provide industrial storage shelving units and racks.
Furnishings
Fixtures &
Equipment
(FF&E)
This space should be adjacent to the Vehicle Maintenance Office and Vehicle Maintenance
Special
Bay.
Requirements
4-16