UFC 4-730-10
15 June 2006
TABLE 4-14.0. DEPLOYMENT GEAR STORAGE
This storage space is utilized for storage of firefighting gear required for military deployment, if
Description/
required by Installation mission requirements (always required for Air Force). This gear may
Usage
be used by reservists and/or active duty military personnel. It includes ventilated lockers with
open shelving.
2.4 m (8 ft.) minimum.
Min. Ceiling Ht.
Walls. CMU. Provide epoxy paints on all wall surfaces.
Floor. Provide a sealed concrete surface.
Ceiling. None required.
None required.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum.
HVAC
Provide Fire Protection System per Paragraph 3-6.3.
Fire Protection
Provide outlets per code.
Power
215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
None required.
Casework
Provide open 600 mm by 600 mm by 1800 mm (24 in. by 24 in. by 6 ft.) high wire mesh metal
Furnishings
lockers that include shelves and clothes hooks.
Fixtures &
Equipment
(FF&E)
Locker layout should permit free air circulation around and throughout clothing.
Special
Requirements
4-17