MIL-HDBK-1005/9A
3.10.11
run on a batch basis, manual control of treatment unit
operations is recommended. Excessive automation should be
avoided. Any automation provided must have full manual backup.
Automatic backwash controls on filtration units and automatic
start-stop control of polymer feed systems on sensing flow to a
DAF/IAF unit are recommended. pH monitoring and automatic
control for chemicals addition are also recommended. On direct
discharge systems consider provision for automatic recycles of
effluent to a LET if oil is detected at higher than permissible
influent and effluent flow and key effluent quality parameters.
Monitoring instrumentation for facilities discharging to
navigable waters should be provided in duplicate for 100 percent
redundancy. Suggested parameter monitoring guidelines are
presented in Table 16.
Table 16
Guidelines for Oily Waste Treatment Monitoring
Parameter
Effluent to POTW
Effluent to Navigable
Waters
Influent flow
Continuously monitor
Continuously monitor
using magnetic type
using magnetic type meter
meter with chart
with chart recorder.
recorder.
Effluent oil
Analysis of grab
Continuously monitor
content
samples taken at
using ultraviolet
intervals required by
transmission/fluorescence
permit.
detection type meter with
chart recorder. Verify
with laboratory analysis
of daily grab or
composite samples.
Effluent pH
Periodic checks taken
Continuously monitor
at intervals required
using submerged
by permit.
probe/remote analyzer
type meter with chart
recorder.
Effluent flow
Continuously monitor
Continuously monitor
using magnetic,
using magnetic, turbine,
turbine, or overflow
or overflow weir/float
weir/float type meter
type meter with chart
with chart recorder.
recorder.
177