e. Interior and exterior acoustical treatment to attain the room criteria
described in Paragraph 3-3.1. Use soft textured acoustical wall
panels in the IFR room.
f.
Cable trays or conduits between the ATCT and the RATCF for
intra-facility cabling. The exact dimensions of the cable trough or
size and number of conduits are specified in the FRS.
2-2.3.1
Windows.
Do not provide windows in IFR or IFR equipment rooms. Provide insulated
glazing for noise reduction in administrative areas. See Paragraph 3-6.3.6.
2-2.4
Electrical Requirements.
2-2.4.1
Uninterrupted Power Supply (UPS).
Provide non-redundant UPS with maintenance bypass switch in accordance with
Paragraph 3-5.2.3. Use the anticipated load to determine the size of the UPS.
ATC electronic equipment loads will be provided in the FRS
2-2.4.2
Emergency Electrical Power.
Provide an emergency generator with automatic starting and switching capability
as described in Paragraph 3-5.2. Provide emergency power to:
a. All loads as required by NFPA-101, Life Safety Code.
b. Electronic equipment in the IFR and IFR equipment rooms.
c.
Mechanical systems supporting electronic equipment.
d. Exterior security lighting and security systems.
2-2.4.3
400-Hz Power.
Provide 400-Hz (Hz) power in accordance with Paragraph 3-5.2.4 when required
by the FRS.
2-2.4.4
Lighting.
Design lighting in accordance with HB-9-00, Lighting Handbook. Provide dimmer
adjustable red or blue lights in the IFR room. See SSCC FRD for additional
information.