Project Name
Project Number
TEMF
Statement of Work
UFC 4-214-02, 24 Jul 03
5-2.5
The [insert name of post] Installation Design Guide (IDG), excerpts of which are
included in an appendix to the Statement of Work.
5-2.6
[Insert any additional regulations known to have an impact on facility design and
construction, such as airfield height limitations; AICUZ/APZ information; historic area
requirements; etc. Include excerpts of the document in an appendix to the SOW, or include
source of availability in Appendix A References.].
5-3
IBC OCCUPANCY AND BUILDING TYPE CLASSIFICATIONS.
5-3.1
General. Occupancy classifications, construction types, allowable areas, maximum
building heights, and fire separation requirements shall comply with the requirements of the
International Building Code.
5-4
EXTERIOR DESIGN.
5-4.1
Acceptable Materials and Colors. Exterior elements of the facilities shall comply
with the Installation Design Guide (IDG) unless required otherwise by applicable codes or this
Statement of Work.
5-4.2
Exterior Walls. Comply with IDG. Where masonry exterior wall finish material is
used, and where allowed by code, concrete masonry or metal stud backup wall may be used.
Exterior insulation finish systems shall not be used [may be used as exterior accent materials,
not primary wall material] [Coordinate with installation facilities engineer (DPW) and edit
appropriately].
5-4.3
Roofs. Sloped roofs with a minimum pitch of [__] : 12 shall be used on all buildings.
Roofing material and color shall comply with IDG. Roofing system shall have Underwriters
Laboratory (UL) Class A rating for fire resistance, UL 90 wind resistance rating, and Factory
5-4.3.1
Metal Roofing. Provide manufacturers 20-year finish warranty.
5-4.3.2
Asphalt Shingle Roofing. Provide minimum 30-year shingles; provide minimum
30# felt underlayment. Provide self-adhering rubberized ice and water shield underlayment at
all valleys, and roof perimeter [review requirement in regard to local climate].
5-4.4
Trim and Flashing. Materials and colors shall comply with IDG. [Review the IDG to
make sure that trim and flashing materials and colors are sufficiently covered.] Gutters,
downspouts, and fascias shall be prefinished metal; comply with SMACNA Architectural Sheet
Metal Manual; provide 20 year manufacturers finish warranty.
5-4.5
Miscellaneous Exterior Elements. Comply with IDG. [review the IDG to make sure
that trim and minor elements are sufficiently covered. It is advisable to prohibit any use of
exterior wood with painted finish; require prefinished metal trim. If not stated in IDG, require
exterior metal railings to be prefinished aluminum, or if acceptable to installation facilities
engineer (DPW), allow the more economical option of using field-painted (and adequately pre-
treated) galvanized steel railings. Coordinate with user to include requirements for any building-
beacons, etc.].
SOW-66