Statement of Work
UFC 4-214-02, 24 Jul 03
of America (TCA) Handbook For Ceramic Tile Installation. Substrate for wall tile shall be mortar
setting bed or cement backer board (gypsum board is not acceptable). Provide marble
threshold under doors where a ceramic tile floor meets a different floor finish.
5-5.4
Ceilings. Comply with requirements of applicable codes. Non-combustible
construction is preferable, even where combustible materials are allowed by code. Ceiling
finish materials shall be as specified in functional and area requirements listed in Chapter 2 of
the Statement of Work.
5-5.5
Interior Doors and Frames. Provide hollow metal doors and frames.
5-5.5.1
Hollow Metal Doors. Comply with ANSI A250.8/SDI 100. Doors shall be Level 2,
physical performance Level B, Model 2; factory primed. Anchors and accessories shall be zinc
coated. Frames in masonry shall have bituminous back-coating, plaster guards, and shall be
grouted solid.
5-5.5.2
Hollow Metal Frames. Comply with ANSI A250.8/SDI 100. Frames shall be Level
2, 16 gauge, with continuously welded corners and seamless face joints; factory primed.
Anchors and accessories shall be zinc coated. Frames in masonry shall have bituminous back-
coating, plaster guards, and shall be grouted solid.
5-5.5.3
Fire-rated and Smoke Control Doors and Frames. Comply with International
Building Code (IBC), NFPA 80, and requirements of labeling authority. Doors and frames shall
bear labels from IBC approved testing laboratory. Comply with positive pressure testing
requirements of IBC.
5-5.5.4
Interior Door Finish Hardware.
5-5.5.4.1 Hinges. ANSI/BHMA A156.1; template, full mortise; heavy duty, ball bearing on
doors with closers; standard duty anti-friction bearing on doors without closers. Minimum size
114mm x 114mm.
5-5.5.4.2 High Security Locksets. [Insert any requirements].
5-5.5.4.3 Locksets on Interior Doors. ANSI/BHMA A156.13; series 1000, Grade 1 mortise
locksets, non-ferrous base metal, removable core.
5-5.5.4.4 Exit (Panic) Devices. ANSI/BHMA 156.3; heavy-duty touch-pad type, through-
bolted mounting. Listed and labeled for panic protection based on UL 305.
5-5.5.4.5 Closers. ANSI/BHMA A156.4; series C02000, Grade 1, hydraulic, factory-sized,
adjustable to meet field conditions. Provide for all entry doors to living units, all doors opening
to corridors and as required by codes.
5-5.5.4.6 Auxiliary Hardware. ANSI/BHMA A156.16. Provide wall or floor stops for all doors
that do not have overhead holder/stops. Provide other hardware as necessary for a complete
installation.
5-5.5.4.7 Kick Plates. ANSI/BHMA A156.6; non-ferrous metal. Provide at all doors with
closers.
SOW-69