UFC 4-214-02, 24 Jul 03
5-5.6
Limitations on Use, Classification, and Flame Spread and Smoke Developed
Ratings of Interior Finishes.
Refer to
paragraph 12-6.2.
5-5.7
Casework.
5-5.7.1
Vanity Countertop at Toilets. Countertops shall be high-pressure plastic laminate
or solid surfacing material, with integral coved backsplash. Substrate shall be two layers of 19
mm thick exterior grade plywood. Reinforce countertop with concealed steel angles so that top
will not deflect more than 5 mm when 115 kg load is applied at mid-span. Comply with AWI
Section 400 Custom Grade requirements.
5-5.7.2
Other casework. Provide architectural casework complying with AWI Section 400,
Custom Grade cabinets with high pressure decorative laminate finish meeting NEMA LD3
standards. Horizontal laminate: nominal 1.27mm thick; vertical laminate: nominal 0.71mm thick.
Door and drawer edges shall be heavy duty 3 mm extruded polyvinyl chloride with self-locking
serrated tongue. Worksurfaces and counter shall be high pressure decorative laminate, or solid
surfacing material.
5-5.8
Window Treatments. Provide horizontal aluminum mini-blinds at all exterior
windows in core areas, except windows and storefront in corridors. Blinds shall have 25.4mm
wide x 0.2mm thick slats with anti-static, anti-microbial polyester baked enamel finish. Provide
heavy duty 25.4mm x 38.1mm steel headrail, and tubular steel bottom rail finished to match
slats.
5-5.9
Interior Signage. Comply with requirements of ADAAG and UFAS. Provide interior
room identification signage for the following spaces: Public toilets, [Coordinate with user and
installation facilities engineer (DPW). List all rooms which require room identification signage;
coordinate with the installation interior signage standard, if one exists].
5-5.10
[Elevators.
The offeror shall provide the services of an
elevator inspector employed
by an independent testing company to inspect the elevator, witness the final testing, and certify
elevator. The inspector shall meet all qualification requirements of ASME QEI-1 and shall be
certified in accordance with ASME QEI-1. The offeror shall provide an elevator certificate
signed by the inspector for each elevator. The certificate shall be provided to the Contracting
Officer within 30 days of the completion of testing.] [Delete if elevator is not required].
5-5.11
Overhead Bridge Cranes. [Coordinate with the using activity. Include the following
requirements for each type/size of crane in the facility: hook height, limits of working envelope,
level of service expected from the system, minimum working characteristics of the crane trolley,
range of speeds, applicable codes and regulations, and other performance criteria].
5-6
PHYSICAL SECURITY REQUIREMENTS.
5-6.1
Anti Terrorism / Force Protection. Comply with the minimum construction
standards of the Department of Defense Antiterrorism Standards for Buildings. [Coordinate with
the installation security forces and facilities engineer to determine if the minimum standards are
adequate for the project location. If a threat analysis has identified a specific threat that
requires more stringent measures than provided by the minimum standards, edit the SOW
criteria accordingly.] TEMF buildings are classified as primary gathering structures
5-6.2
Weapons [and COMSEC] Vaults. [Include design criteria here, or as an attachment
SOW-70