5-4.6
Signage. Comply with IDG. [Coordinate with installation facilities engineer (DPW);
provide criteria for quantity, type, size and location of building identification signs. Note whether
5-4.7
Exterior Personnel Doors and Frames.
5-4.7.1
Main Entrance Doors. Doors opening to building corridors or lobbies shall be
aluminum storefront doors and frames with Architectural Class I anodic finish or AAMA 2605
organic coating finish. Color shall comply with IDG. Doors shall be minimum 45 mm thick.
Fully glazed stile and rail doors shall be medium or wide stile. Provide aluminum storefront
systems that comply with wind load requirements of applicable codes. Framing systems shall
have thermal-break design.
5-4.7.2
Exterior Non-entrance Doors. Exterior doors and frames opening to spaces other
than corridors or lobbies shall be hollow metal; comply with ANSI A250.8/SDI 100. Doors shall
be Level 3, physical performance Level A, Model 2; insulated; top edge closed flush. Frames
shall be Level 3, 14 gauge, with continuously welded corners and seamless face joints. Doors
and frames shall be constructed of hot dipped zinc coated steel sheet, complying with ASTM
A653, Commercial Steel, Type B, minimum A40 coating weight; factory primed. Anchors and
accessories shall be zinc coated. Frames in masonry shall have bituminous back-coating,
plaster guards, and shall be grouted solid. Fire-rated openings shall comply with NFPA 80, and
the requirements of the labeling authority.
5-4.7.3
Exterior Door Finish Hardware.
5-4.7.3.1 Hinges. ANSI/BHMA A156.1; template, full mortise, heavy duty, ball bearing,
minimum size 114mm x 114mm, non-ferrous base metal, non-removable pins.
5-4.7.3.2 Locksets. ANSI/BHMA A156.13; series 1000, Grade 1 mortise locksets, non-
ferrous base metal, removable core.
5-4.7.3.3 Exit (Panic) Devices. ANSI/BHMA 156.3; heavy-duty touch-pad type, through-
bolted mounting. Listed and labeled for panic protection based on UL 305.
5-4.7.3.4 Closers. ANSI/BHMA A156.4; series C02000, Grade 1, hydraulic, factory-sized,
adjustable to meet field conditions. Provide for all exterior doors, [coordinate additional closer
locations with user] all doors opening to corridors, and as required by codes. At all exterior
doors provide overhead holders or closers with hold-open capability.
5-4.7.3.5 Auxiliary Hardware. ANSI/BHMA A156.16. Provide wall or floor stops for all
exterior doors that do not have overhead holder/stops. Provide other hardware as necessary
for a complete installation.
5-4.7.3.6 Thresholds. ANSI/BHMA A156.21; non-ferrous metal. Provide at all exterior doors.
5-4.7.3.7 Weatherstripping. ANSI/BHMA A156.22. Provide at all exterior doors.
5-4.7.3.8 Kick Plates. ANSI/BHMA A156.6; non-ferrous metal. Provide at all doors with
closers.
5-4.8
Overhead Doors. [Insert requirements]