TABLE 4-3.0. HOSE STORAGE
This area provides for storage of hoses. Hoses are rolled and stored on fixed or mobile storage
Description/
racks.
Usage
2.4 m (8 ft.) minimum.
Min. Ceiling Ht.
Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex or epoxy
paints on all wall surfaces.
Floor. Provide a sealed concrete surface sloped to floor drain.
Ceiling. None required.
Provide a floor drain. Consider providing a hose bibb.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum. Well ventilated.
HVAC
Provide Fire Protection System per Paragraph 3-6.3.
Fire Protection
Provide outlets per code and dedicated outlets required to support drying equipment (if
Power
provided).
540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
None required.
Casework
Provide movable racks for roll-up hose storage. Consider providing hose drying oven in areas
Furnishings
where required by climatic conditions.
Fixtures &
Equipment
(FF&E)
Special
Requirements