UFC 4-730-10
15 June 2006
TABLE 4-8.0. HAZMAT/CBRNE EQUIPMENT STORAGE
HAZMAT/CBRNE Equipment Storage is a separate storage facility housing only equipment
Description/
classified for use with hazardous materials. Provide sufficient floor and open shelf storage
Usage
areas.
2.4 m (8 ft.) minimum.
Min. Ceiling Ht.
Walls. CMU. Provide a low-maintenance, durable finish such as industrial latex paint.
Floor. Provide a sealed concrete surface. A non-skid, low-maintenance traffic coating may
also be acceptable.
Ceiling. None required.
None required.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum. This room should be negatively pressurized with
HVAC
dedicated exhaust vented to the outside.
Provide Fire Protection System per Paragraph 3-6.3.
Fire Protection
Provide outlets per code.
Power
215 Lux (20 ft. candles). Provide fluorescent energy efficient light fixtures.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
None required.
Casework
Provide industrial storage shelving units and racks.
Furnishings
Fixtures &
Equip. (FF&E)
Special
Requirements
4-9