UFC 4-730-10
15 June 2006
TABLE 4-20.0. TESTING/INDIVIDUAL STUDY AREA
This area consists of individual computer/study carols for study and testing of firefighters.
Description/
Each of these stations must be private to eliminate potential for cheating during testing and to
Usage
facilitate quiet study. See Figure D-5 for a sample layout of this space.
2.4 m (8 ft.) minimum.
Min. Ceiling Ht.
Walls. Provide a low-maintenance, durable finish such as egg-shell latex paint.
Floor. Provide low-maintenance sheet or tile vinyl flooring material with rubber base.
Consider providing durable commercial carpeting.
Ceiling. Provide ACP ceiling.
None required.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum. Consider providing separate thermostat for this
HVAC
room.
Provide Fire Protection System per Paragraph 3-6.3.
Fire Protection
Provide outlets per code. Provide direct power to each computer/study carol and for other
Power
540 Lux (50 ft. candles). Provide fluorescent energy efficient light fixtures.
Lighting
CCTV. Provide video camera with monitor located in Testing Officer Office.
Communication
CATV/Internal Video. None required.
PA/Audio. Provide a speaker
Telephone. None required.
Data. Provide data outlets to all workstations and equipment.
Security. None required.
None required.
Casework
Provide four computer/study carols (to accommodate one company) and printer(s), office
Furnishings
chairs, and task lights.
Fixtures &
Equipment
(FF&E)
Provide a minimum STC rating of 50 to 55.
Special
Requirements
4-23