UFC 3-600-02
1 January 2001
2-2.11
Hydrants and Monitors. Technical guidance on the tasks in Table 2-12 is
contained in NFPA 25.
Table 2-12. Hydrants and Monitors ITM Tasks
Component
Task
2 Years
1. Hydrants
1. Inspect for accessibility, leaks, and
worn threads.
2. Operate to ensure proper functioning.
4. Lubricate hydrant to ensure ease of
operation.
2. Yard Monitor Nozzles
1. Inspect for condition.
2. Conduct flow test to verify proper
function and range of motion.
3. Lubricate to ensure proper operating
conditions.
3. Hose Houses
1. Inspect for accessibility and physical
condition.
2. Verify inventory and its condition.
5 Years
1. Underground and
1. Conduct flow tests.
Exposed Piping.
After Flow
1. Strainers
1. Inspect and clean after each flow.
2-2.12
Fire Pumps. Technical guidance on these tasks is contained in NFPA 20 and
NFPA 25.
Table 2-13. Fire Pumps ITM Tasks
Component
Tasks
Monthly
1. Pump House
1. Inspect for proper condition, ventilation
2. Control Valve and
1. Verify proper valve position.
Isolation Valve
3. Pressure Gauges
1. Check reading and verify gauge
operability.
2-17