UFC 3-600-02
1 January 2001
Table 2-14. Water Supply Tanks ITM Tasks (Continued)
Component
Tasks
5 Years
1. Tanks (with cathodic
1. Conduct internal tank inspection to
protection)
determine condition and amount of
corrosion.
2. Pressure Gauges
1. Calibrate gauges.
3. Check Valves
1. Inspect interior of valves.
4. Level Indicator Test
1. Calibrate level indicator.
2-2.14
Dry Chemical Systems. Detection devices for actuation are addressed in
paragraph 2-2.2. Technical guidance on these tasks is contained in NFPA 17.
Table 2-15. Dry Chemical Systems ITM Tasks
Component
Tasks
Semi-
1. Piping
1. Inspect piping for obstructions
Annual
and proper support.
2. Storage Vessels
1. Inspect agent container for
condition.
2. Verify storage pressure of
propellant.
3. Agent
1. Verify quantity and quality of
agent.
4. Actuators
1. Inspect manual actuators for
accessibility.
2. Inspect detection devices (fusible
3. Test actuation system without
agent release.
shutoff) operate properly.
1. Replace detection devices
Annual
1. Actuators
5-12 Years
1. Storage Vessels
1. Conduct hydrostatic test for
pressure cylinders in accordance
with OSHA and DOT standards.
2-20