UFC 3-600-02
1 January 2001
2-2.17
Clean Agent Systems. Detection devices for actuation are addressed in
paragraph 2-2.2. Technical guidance on the tasks is contained in NFPA 2001.
Table 2-18. Clean Agent Systems ITM Tasks
Component
Tasks
Annual
1. Piping
1. Inspect piping and nozzles for
condition and orientation.
2. Flexible Hoses
1. Inspect for damage.
3. Storage Vessels
1. Inspect storage containers'
exterior (tanks, spheres,
cylinders).
4. Agent and Propellant
1. Verify adequate quantity of agent.
2. Verify adequate pressure of
agent/propellant.
5. Actuators
1. Inspect manual actuators for
accessibility.
2. Test actuation without agent
release.
6. Auxiliary Equipment
(equipment shutdown, dampers,
door closures) operate properly
and are activated by the system
actuation.
7. Valves
1. Verify valves in proper alignment.
2 Years
1. Protected Enclosure
1. Inspect the enclosure to verify
(Room)
integrity and ability to maintain
(and after
agent concentration.
modifications to
compartment)
5 Years
1. Cylinders
1. Perform complete external
inspection of non-discharged
cylinders to ensure suitability for
use.
2. Flexible Hoses
1. Pressure-test hoses to ensure
suitability for use.
2-24