UFC 4-740-03
1 NOVEMBER 2002
TABLE 3-15. OUTSIDE GEAR WASH
Cleaning of all rental equipment that is to be stored in the outside equipment storage
Description/
areas only.
Usage
2.74 m (9 ft.) minimum if covered.
Min. Ceiling Ht.
Walls. None.
Floor. Sealed Concrete.
Ceiling. None.
Plumbing
Water supply for washers, spray units, and service sinks. Provide additional floor
drains in wash areas.
None required.
HVAC
None required. Verify if covering is provided.
Fire Protection
Power
Provide waterproof outlets per code. Provided additional outlets as necessary to
operate dedicated equipment.
None required.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. None required.
Telephone. None required.
Data. None required.
Security. None required.
None required.
Casework
Pressure washers.
Furnishings
Fixtures &
Equipment
(FF&E)
Provide curbs at wash areas to contain water. Slope floors minimum of 1 percent (.125
Special
in. per 12 in.) to all floor drains. Consider covering if budget allows. Provide oil/water
Requirements
separator where equipment using hydrocarbon fuels or lubricants is to be washed.
3-18