UFC 4-740-03
1 NOVEMBER 2002
TABLE 3-14. INSIDE GEAR WASH
Cleaning of all rental equipment that is to be stored in the inside equipment storage
Description/
areas only.
Usage
2.74 m (9 ft.) minimum.
Min. Ceiling Ht.
Walls. Painted gypsum wallboard. In areas subject to spray washing, consider fiber
reinforced epoxy coated CMU or Cement Backer Board.
Floor. Sealed Concrete.
Ceiling. None.
Water supply for washers, spray units, and service sinks. Provide general floor drains.
Plumbing
Provide additional floor drains in wash areas.
20 C (68 F) minimum, 26 C (78 F) maximum. Exhaust for clothes dryers.
HVAC
Building system.
Fire Protection
Power
Provide waterproof outlets per code. Provide additional outlets as necessary to operate
dedicated equipment.
1080 Lux (100 ft. candles). Consider waterproof luminaries.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. Provide a speaker.
Telephone. None required.
Data. None required.
Security. None required.
None required.
Casework
Commercial grade washers and dryers.
Furnishings
Fixtures &
Tables for folding clothing.
Equipment
Pressure washers.
(FF&E)
Provide curbs at wash areas to contain water. Slope floors minimum of 1 percent (.125
Special
in. per 12 in.) to all floor drains.
Requirements
3-17