UFC 4-740-03
1 NOVEMBER 2002
TABLE 3-13. EQUIPMENT REPAIR WITH DROP-OFF
Repair area for all types of equipment that is rented. Storage area for tools and some
Description/
commonly used parts. Equipment pick-up and return area where equipment is
Usage
checked for damage, cleaned, then returned to rental stock.
2.74 m (9 ft.) minimum.
Min. Ceiling Ht.
Walls. Painted gypsum wallboard with modular "peg-type" backboard for hanging tools
and equipment. Also consider painted CMU or fiber cement paneling.
Floor. Sealed concrete.
Ceiling. None.
Floor drain.
Plumbing
20 C (68 F) minimum, 26 C (78 F) maximum.
HVAC
Building system.
Fire Protection
Power
Provide outlets per code. Provide additional outlets for convenience and as necessary
for the operation of dedicated equipment.
Provide 220v outlets/circuits as necessary for the operation of dedicated equipment
such as ski tuners, arc welders, etc.
1080 Lux (100 ft. candles) with additional adjustable task lights.
Lighting
CCTV. None required.
Communication
CATV/Internal Video. None required.
PA/Audio. Provide one speaker.
Telephone. Provide one line.
Data. Provide one line.
Security. None required.
Plastic laminate countertop as writing surface and computer area.
Casework
Shelving for parts storage.
Workbenches with drawers.
Furnishings
Fixtures &
Modular, lockable cabinets for the storage of tools and valuable parts.
Equipment
Chairs.
(FF&E)
Minimum 1830 mm (6 ft.) wide opening to adjacent storage and exterior drop off area.
Special
Consider roll-up doors, budget permitting.
Requirements
Consider a covered drop off.
3-16