UFC 4-171-05
1 January 2005
with change 25 October 2006
Architectural/Interiors
Minimum STC rating 40
Ceiling height 14 ft (4300 mm)
Floor VCT; concrete with sealer or paint if truck access
Base rubber
Walls painted gypsum board; painted CMU if truck access
Ceiling suspended acoustical ceiling tile (ACT); none if truck access
Trim \ none/2/
Lockset panic hardware
Figure 4-11
Assembly Hall and Kitchen
Mechanical
Heating, occupied 68 degrees F (20 C); maintained 55 degrees F (13 C)
Cooling, occupied 78 degrees F (25 C); maintained ambient
Ventilation comply with ASHRAE 62.1
electrical
Lighting 50 fc; dual-level switching
Voice/data two voice/data duplexes per wall
92