4-2.45.3 Space Design Information
General/Code
Size 360 sf (33.5 sq m))
Occupancy business
Occupancy count not occupied; typically 1 person per 300 sf (27.9 sq m)
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor concrete, sealed
Base none
Walls sealed and painted CMU; painted gypsum board as an alternative
Ceiling none, paint structure
Trim none
Lockset storeroom
Mechanical
Cooling ventilate sufficient to remove excess equipment heat
Ventilation sufficient to maintain suitable temperatures for equipment
electrical
Lighting 30 fc
Voice/data wall phone
Furniture
equipment
Electrical service equipment
special features or considerations
Main ground bar
Ordinary hazard sprinkler
Avoid routing water piping above electrical equipment
4-2.46
Telephone
4-2.46.1 The main telephone service room should also be a dedicated space, not
shared with mechanical or electrical equipment. This is the utility service entrance, and
the demarcation point between utility and Government telephone system ownership.
4-2.46.2 Space Design Information
General/Code
Size 100 sf (9.3 sq m)
Occupancy business
Occupancy count not occupied; typically 1 person per 300 (27.9 sq m)
Architectural/Interiors
Minimum STC rating 40
Ceiling height
Floor concrete, sealed