UFC 4-171-05
1 January 2005
with change 25 October 2006
armorer s and arms vault spaces in a training center.
Figure 4-41
Small Arms Repair Room with Arms Vault
4-5.3.2
A 110 volt continuous power strip should be provided over the work benches.
4-5.3.3 Construction of the vault must be in compliance with AR 190-11. See Section
4-2.11 for additional vault design information.
4-5.3.4 Space Design Information: Refer to arms vault and armorer s room, Sections
4-2.11 and 4-2.12 above. Provide air conditioning.
4-5.4
Supply
4-5.4.1 This space is provided for the storage, receipt and issue of spare parts for
AMSA maintenance and operations. It is a part of the tools and parts room, but should
be separated from the tools and parts with standard caging.
4-5.4.2 Space Design Information: Same as OMS tools and parts storage, Section
4-3.3 above.
4-5.4.3 A supply office may be provided adjacent to the supply space. The design
criteria are the same as those for an OMS office space, Section 4-3.1 above.
4-5.5
4-5.5.1 This space is provided for the repair and storage of supported units
4-5.5.2 Space Design Information: Same as armorer s room, Section 4-2.12 above.
Provide air conditioning, provide continuous 110V power strip above workbench, and
144