11.2.3 Architectural
11.2.3.1 Design narrative shall provide a summary of functional space relationships, as well as circulation.
There shall also be a general statement for the rationale behind the major design decisions.
11.2.3.2 Architectural Floor Plans shall indicate dimensions, columns lines, and detail references. Toilets
and other specialized areas shall be drawn to 1/4" scale and shall show any needed interior features.
11.2.3.3 Finish schedule shall indicate material, finishes, colors and any special interior design features
such as soffits, fascias, and lighting troughs, etc.
11.2.3.4 All required equipment shall be shown on the drawings with an equipment list.
11.2.3.5 List any special graphics requirements that will be provided.
11.2.3.6 Schedules shall be provided for both doors and windows. These schedules shall indicate sizes,
types, and details for all items shown on floor plans.
11.2.3.7 Hardware sets using BHMA designations.
11.2.3.8 Composite floor plan showing all prewired workstations. Also show typical elevations of each
type of workstation.
11.2.3.9 SID package.
11.2.3.10 Fire Protection and Life Safety Analysis. This analysis must be performed by a Registered Fire
Protection Engineer (FPE). NICET certification is not sufficient to address this requirement.
11.2.4 Structural Systems
11.2.4.1 State the live loads to be used for design. Include roof and floor loads; wind loads, lateral
earth pressure loads, seismic loads, etc., as applicable.
11.2.4.2 Describe the method of providing lateral stability for the structural system to meet seismic
and wind load requirements. Include sufficient calculations to verify the adequacy of the method.
11.2.4.3 Furnish calculations for all principal roof, floor, and foundation members.
11.2.4.4 This submittal shall include drawings showing roof and floor framing plans as applicable.
Principal members will be shown on the plans. A foundation plan shall also be furnished showing
main footings and grade beams where applicable. Where beam, column, and footing schedules are
used, show schedules and fill in sufficient items to indicate method to be used. Show typical bar
bending diagram if applicable. Typical sections shall be furnished for roof, floor, and foundation
conditions. Structural drawings for proposals and submittals shall be separate from architectural
drawings.
11.2.4.5 Provide any computer analyses used shall be widely accepted, commercially available
programs and complete documentation of the input and output of the program.
11.2.4.6 Provide complete seismic analyses for all building structural components. Seismic
calculations shall clearly demonstrate compliance with all requirements set forth in the Statement of
Work.
11.2.5 Plumbing Systems