UFC 4-214-02, TEMF, 24 Jul 03
Efficiency (if applicable)
Manufacturer's name
Optional features to be provided
Physical size
11.3.8.1.3 Details: Construction details, sections, elevations, etc., shall be provided where required for
clarification of methods and materials of design. Roof and exterior wall penetrations shall be detailed
on the drawings.
11.3.8.2 Plumbing Floor Plan: The floor plan shall show all principal architectural features of the
building which will affect the plumbing design. Separate plumbing plans will not be required if
sufficient information can be shown on the mechanical plans to meet the requirements shown above.
The floor plan shall also show the following:
Room designations.
Fixture Schedule.
Location of utility entrances.
Waste and water pipe location and size.
Fixture designations.
11.3.8.3 Design Analysis: Complete design calculations for mechanical systems. Include
computations for sizing PM&E equipment, air duct design, and U-factors for ceilings, roofs and exterior
walls and floors. Contractor shall employ commercially available energy analysis techniques to
determine the energy performance of all passive systems and features. Use of hourly energy load
computer simulation (e.g., TRNSYS, DOE 2.1 Blast, etc.) is required. These calculations can be used
to size the mechanical systems. Based on the results of calculations, provide a complete list of the
materials and equipment proposed for heating and plumbing, with the manufacturer's published
cataloged product installation specifications and roughing-in data. The heating and cooling equipment
data shall include the manufacturer's wiring diagrams, installation specifications, ARI certification, and
the standard warranty for the equipment.
11.3.9 Specific Electrical Requirements:
11.3.9.1 Required Plans, Diagrams, Schedules, and Details on Unit Electrical Drawings:
11.3.9.1.1. Electrical Floor Plan. The floor plans shall show all principle architectural features of the
building which will affect the electrical design. The floor plan shall also show the following:
Room designations.
Electrical legend and applicable notes.
Lighting fixtures, properly identified.
Location of telephone and cable TV outlets.
Switches for control of lighting.
Location and designation of panelboards. Plans should clearly indicate type of mounting
required (flush or surface) and be reflected accordingly in specifications. Service entrance
(conduit and main disconnect).
Location, designation and rating of motors and/or equipment which requires electrical service.
Show method of termination and/or connection to motors and/or equipment. Show necessary
junction boxes, disconnects, controllers (approximate only), conduit stubs, and receptacles
required to serve the motor and/or equipment.
Indicate the types and sizes of electrical equipment and wiring. Include grounding and metering
requirements.
Section 01012 - Page 15