UFC 4-214-02, TEMF, 24 Jul 03
component inventory. Prewired workstation panel identification plan with electrical outlet placement
including base feed.
11.3.5.3 SID package.
11.3.5.4 Fire Protection and Life Safety Analysis. This analysis must be performed by a Registered
Fire Protection Engineer (FPE). NICET certification is not sufficient to address this requirement.
11.3.6 Structural Design
11.3.6.1 Furnish complete checked calculations for all structural members. Incorporate any changes
required by comments on 50% Design Submittal.
11.3.6.2 Prior to this submittal, structural drawings shall be coordinated with all other design
disciplines.
11.3.6.3 The final structural drawings shall contain the following information as a set of general notes:
The allowable soil bearing value.
The design stresses of structural materials used.
The design live loads used in the design of various portions of the structures.
The design wind speed.
The seismic zone and the "K", "C", "I" and "Z" values used in design.
11.3.6.4 All structural drawings and calculations shall be checked and stamped by the designer of
record (a registered Professional Engineer).
11.3.7 Fire Sprinkler System: Provide a file of the input data used in the computer program to design
the fire sprinkler system as well as the output data.
11.3.8 Specific Mechanical and Plumbing Requirements:
11.3.8.1 Required Plans, Diagrams, Schedules and Details on Unit Mechanical Drawings:
11.3.8.1.1. Mechanical Floor Plan: The floor plans shall show all principle architectural features of the
building which will affect the mechanical design. The floor plans shall also show the following:
Room designations.
Mechanical legend and applicable notes.
Location of all ductwork or piping (double line ductwork required).
Location and capacity of all terminal units (i.e., registers, diffusers, grilles, hydronic baseboards).
Exhaust fan and range hood location.
Size of all ductwork and piping.
Thermostat location.
Location of heating/cooling plant (i.e., boiler, chiller, cooling tower, etc).
Location of all air handling equipment.
Return air paths (i.e., undercut doors, transfer grilles).
Flue piping size and location.
Piping diagram for forced hot water system (if used).
Fuel supply and return piping
11.3.8.1.2. Equipment Schedule: Complete equipment Schedules shall be provided. Schedule shall
also include:
Capacity
Electrical characteristics
Section 01012 - Page 14