Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
2-4.7.2.8 Adjacency requirements: Adjacent to lobby or corridor. Adjacent to PAC private
offices and Message Mail Center. Near Duty Officer.
2-4.7.2.9 Furnishings/Fixtures/Equipment: Provide and design room to accommodate eight
type [___] systems furniture workstations.
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-4.7.3
Other requirements: Provide 914 mm [3'-0"] wide door into room; door shall have
entry function (F81) lockset. Exterior window is desirable. Partitions shall have minimum STC
rating of 49. Minimum ceiling height 2642 mm [8'-8"].
Duty Officer. Provide one; 8.8 m2 [95 sf]. Room shall be accessed from the main
2-4.7.4
lobby. Occupants: 1.
2-4.7.4.1 Function: Duty Officer will provide physical security of the building, and visual control
of the entrances and lobby, as well as functioning as an information source for visitors.
2-4.7.4.2 Adjacency requirements: Adjacent to lobby and main entrance; near PAC Clerical
/Central Files.
2-4.7.4.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate one
desk [____] with return [____], one legal-size four-drawer file cabinet, one side chair, and one
desk chair.
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-4.7.4.5 Other requirements: Provide 914 mm [3'-0"] wide door into room; door shall have
entry function (F81) lockset and glass vision panel. Provide duty officer counter (built-in
casework) minimum 1829 mm [6'-0"] long separating the Duty Officer room from the
lobby/corridor. The counter on the corridor side shall be minimum 1524 mm [5'-0"] wide x 1016
mm [3'-4"] high x 305 mm [12"] deep; provide locking overhead coiling shutter to secure the
opening when unattended; shutter hood shall not be visible from corridor side. [modify
requirement for sliding pass-through window above counter if requested by user].
Message Mail Center. Provide one; 8.8 m2 [95 sf]. Room shall be accessed from
2-4.7.5
the PAC Clerical/Central Files area. Occupants: [___].
2-4.7.5.1 Function: Mail sorting [add to description of function].
2-4.7.5.2 Adjacency requirements: Adjacent to corridor and PAC Clerical /Central Files.
SOW-51