Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
will be located on the first floor. Occupants: up to 22 persons [verify with user].
2-4.9.2.1 Function: Soldier training and other meetings.
2-4.9.2.2 Adjacency requirements: Adjacent to lobby or main corridor. Near classrooms and
toilets.
2-4.9.2.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate
[Coordinate furniture requirements with user]. Partitions shall have minimum STC rating of 49.
Provide one marker board (minimum 2438 mm wide x 1219 mm high [8'-0" x 4'-0"]) and one
2438 mm wide [8'-0"] wall mounted pull-down projection screen.
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling, and painted gypsum wallboard or painted veneer
plaster
2-4.9.2.5 Other requirements: Provide 914 mm [3'-0"] wide doors into room; doors shall have
classroom function (F84) lockset. Permanent partitions shall have minimum STC rating of 49.
Minimum ceiling height 2642 mm [8'-8"] at perimeter, 3048 mm [10'-0"] in main portion of room.
2-4.10
Battalion HQ Common Areas. Provide the following areas in each building.
Handicapped accessibility is required in all common areas except janitor closet and shower
rooms.
2-4.10.1 Lobby and Corridors. Provide as required to allow access to building spaces.
Unless otherwise required, minimum width of main corridors providing access to classroom area
shall not be less than 2438 mm [8'-0"]; minimum width of other main corridors shall not be less
than 1829 mm [6'-0"]. Corridor width shall comply with applicable egress codes.
2-4.10.1.1 Function: Entry to the facility; egress and circulation through the building.
2-4.10.1.2 Adjacency requirements: Adjacent to main entrances and vertical circulation. It is
preferable to enter lobby/main corridor from two sides of the building.
2-4.10.1.3 Furnishings/Fixtures/Equipment: Provide wall mounted electric water cooler. Provide
mechanical and electrical systems to comply with applicable codes. Provide fire extinguishers
in semi-recessed fire extinguisher cabinets to comply with applicable codes. Provide recessed
space for three vending machines per building (machines are not in contract). Provide interior
signage to identify major spaces. Provide two recessed trophy cases (minimum size: 2438 mm
wide x 1524 high x 406 mm deep) per battalion; provide one recessed building directory near
each main entrance; in a two-story building, provide one recessed building directory near
second floor elevator doors. Provide one 1219 mm high x 1829 mm wide [4'-0" x 6'-0"] wall
mounted bulletin board.
Floor: porcelain tile, vinyl composition tile, or carpet.
Base: porcelain tile, stained wood base, or resilient cove base.
Walls: painted gypsum wallboard, or painted veneer plaster.
SOW-54