Statement of Work
26 November 2001
desk [____] with return [____], one bookcase [___],one desk chair, and [insert furniture
requirements].
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-4.8.2.5 Other requirements: Provide 914 mm [3'-0"] wide door into room; door shall have
entry function (F81) lockset. Room shall have exterior window. Partitions shall have minimum
STC rating of 55.
2-4.9
Classroom Areas. Provide one group of classrooms and adjacent Learning
Resource Center for each battalion. In a two-story building locate Classroom Area on the first
floor. Classrooms and Learning Resource Center will be accessed from the lobby or main
corridor. The three classrooms shall be divided by operable panel partitions and provided with
appropriate entrances and exits to allow two or three rooms to be combined for use as one large
classroom.
Classroom. Provide three; minimum area 86 m2 [926 sf] each. Each classroom
2-4.9.1
shall be located to allow direct access from the main corridor/lobby, and direct egress out of the
building. In a two-story building, classrooms will be located on the first floor. Occupants: up to
60 persons in each room [verify with user].
2-4.9.1.1 Function: Soldier training and other meetings.
2-4.9.1.2 Adjacency requirements: Adjacent to lobby or main corridor; adjacent to exterior wall.
Locate all three classrooms together to allow use as larger room. Near toilets.
2-4.9.1.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate
[Coordinate furniture requirements with user]. Walls separating classrooms shall be operable
panel partitions with minimum STC rating of 47. Provide one marker board (minimum 3658 mm
wide x 1219 mm high [12'-0" x 4'-0"]) and one 2438 mm wide [8'-0"] wall mounted pull-down
projection screen [Coordinate with user and add requirements for cable television outlets,
television support brackets, or other equipment; identify whether equipment is to be contractor
or government provided].
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling, and painted gypsum wallboard or painted veneer
plaster
2-4.9.1.5 Other requirements: Provide 914 mm [3'-0"] wide doors into room; doors shall have
classroom function (F84) lockset. Permanent partitions shall have minimum STC rating of 49.
Minimum ceiling height 2642 mm [8'-8"] at perimeter, 3048 mm [10'-0"] in main portion of room.
Learning Resource Center. Provide one; minimum area 31.6 m2 [340 sf]. Provide
2-4.9.2
direct access from the main corridor/lobby. In a two-story building, Learning Resource Center