Project Name
Project Number
UEPH Complex
Statement of Work
26 November 2001
2-4.11.2.4 Finishes: Floor: sealed concrete
Base: resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: none required.
2-4.11.2.5 Other requirements: Electrical service to buildings shall be underground. Doors
shall have storeroom function (F86) locksets.
2-4.11.3 Communication Room. Provide dedicated room(s) for communication distribution
equipment. Each room shall be dedicated to a single battalion, and shall not be combined with
mechanical or electrical rooms. Provide each battalion with one main communication room;
minimum size 3048 mm [10'-0"] x 3353 mm [11'-0"]. In two-story buildings, the communication
room shall be located on the second floor. Provide additional communication rooms as needed; all
spaces having telephone or computer data outlets shall be located to allow a maximum cable length
of 90 m [295 feet] between outlet and communication room. Minimum dimensions of secondary
communication rooms shall be 2134 mm [7;-0"] x 3048 mm [10'-0"]. Provide floor openings and
vertical shaft spaces as necessary. Rooms shall be accessed from corridors. Access will be limited
to authorized personnel.
2-4.11.3.1 Function: Distribution areas for telephone, data network, and cable television.
2-4.11.3.2 Adjacency requirements: Adjacent to corridor. Locate to allow efficient distribution.
2-4.11.3.3 Furnishings/Fixtures/Equipment: As required by Statement of Work.
Base: resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: painted gypsum wallboard, painted veneer plaster, or suspended acoustical panel ceiling
2-4.11.3.5 Other requirements: Door shall have minimum 914 mm [3'-0"] wide door with
storeroom function (F86) lockset. Provide three 102 mm [4"] cempty conduits connecting
vertically stacked communication rooms.
2-4.11.4 Elevator Machine Room. Provide one in each two-story battalion HQ building. Size
to comply with equipment and code requirements.
2-4.11.4.1 Function: Space for hydraulic elevator equipment.
2-4.11.4.2 Adjacency requirements: Adjacent to elevator and corridor.
2-4.11.4.3 Furnishings/Fixtures/Equipment: As required by Statement of Work
2-4.11.4.4 Finishes: Floor: sealed concrete
Base: resilient cove base
Walls: painted gypsum wallboard or painted veneer plaster, or painted concrete masonry units
Ceiling: none required.
2-4.11.4.5 Other requirements:
SOW-59