systems furniture workstation accessed through the S-1/PAC Clerical/Central Files area.
Occupants: 1 in each office [verify with user].
2-5.2.2.1 Function: Private office for use by S-1/PAC personnel.
2-5.2.2.2 Adjacency requirements: Adjacent to S-1/PAC Clerical /Central Files.
2-5.2.2.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate one
desk [____] with return [____], one bookcase [___], two legal-size four-drawer file cabinets, one
side chair, and one desk chair. If systems furniture panels are provided in lieu of drywall
partitions, provide workstation type ___.
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-5.2.2.5 Other requirements: Exterior window is desirable. If drywall partitions are used,
provide 914 mm [3'-0"] wide door into each room; door shall have entry function (F81) lockset.
Drywall partitions shall have minimum STC rating of 49.
S-1/PAC Clerical/Central Files. Provide one; 113 m2 [1,216 sf]. S-1
2-5.2.3
Clerical/Central Files shall be accessed from the lobby or corridor. The area shall have direct
access to S-1/PAC and Command Section private offices. Occupants: 10 staff and occasional
visitors.
2-5.2.3.1 Function: Open office area for S-1/PAC admin staff; access to S-1/PAC and
Command offices.
2-5.2.3.2 Adjacency requirements: Adjacent to lobby or corridor. Adjacent to S-1/PAC and
Command private offices.
2-5.2.3.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate ten type
[___] systems furniture workstations.
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-5.2.3.5 Other requirements: Provide 914 mm [3'-0"] wide door into room; door shall have
entry function (F81) lockset. Exterior window is desirable. Partitions shall have minimum STC
rating of 49. Minimum ceiling height 2642 mm [8'-8"].
Duty Officer. Provide one; 8.9 m2 [96 sf]. Room shall be located to have visual
2-5.2.4
control of the lobby/main corridor. Occupants: 1.
2-5.2.4.1 Function: Duty Officer will provide physical security of the building, and visual control
of the entrances and lobby, as well as functioning as an information source for visitors.