UEPH Complex
Statement of Work
26 November 2001
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-5.3.2.5 Other requirements: Room shall have exterior window. Provide 914 mm [3'-0"] wide
door into room; door shall have entry function (F81) lockset. Partitions shall have minimum STC
rating of 49.
Office. Provide one; each 8.8 m2 [95 sf]. Area may be a private office or a systems
2-5.3.3
furniture workstation accessed through the S-2 Clerical/Central Files area. Occupants: 1 [verify
with user].
2-5.3.3.1 Function: Private office for use by S-2 personnel.
2-5.3.3.2 Adjacency requirements: Adjacent to S-2 Clerical /Central Files.
2-5.3.3.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate one
desk [____] with return [____], one bookcase [___], two legal-size four-drawer file cabinets, one
side chair, and one desk chair. If systems furniture panels are provided in lieu of drywall
partitions, provide workstation type ___.
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-5.3.3.5 Other requirements: Exterior window is desirable. If drywall partitions are used,
provide 914 mm [3'-0"] wide door into each room; door shall have entry function (F81) lockset.
Drywall partitions shall have minimum STC rating of 49.
S-2 Clerical/Central Files. Provide one; 36 m2 [388 sf]. S-2 Clerical/Central Files
2-5.3.4
shall be accessed from the lobby or corridor. The area shall have direct access to S-2 private
offices, Secured Documents Vault, and Signal office. Occupants: 4 staff, and occasional
visitors.
2-5.3.4.1 Function: Open office area for S-2 admin staff; access to other S-2 spaces.
2-5.3.4.2 Adjacency requirements: Adjacent to lobby or corridor. Adjacent to S-2 private
offices, Signal office, and Secured Documents Vault.
2-5.3.4.3 Furnishings/Fixtures/Equipment: Provide and design room to accommodate four type
[___] systems furniture workstations.
Floor: carpet
Base: resilient base
Walls: painted gypsum wallboard or painted veneer plaster
Ceiling: suspended acoustical panel ceiling
2-5.3.4.5 Other requirements: Provide 914 mm [3'-0"] wide door into room; door shall have
SOW-67